infiNET EX Thermostat, Fan Coil Unit, White textured

Get Custom Programming from 4TEC

Price: $575.00
    Quantity:
    Availability: In Stock
    Usually ships In 24 - 48 hours

    Item #: CHV-TSTATEX FCU-W-T

    Description

    The CHV-TSTAtext is a wireless thermostat featuring infiNET EX technology. The CHV-TSTAtext installs just like a conventional thermostat because no extra wires are needed to connect to the control system. Although functional as a standalone thermostat, the CHV-TSTAtext delivers enhanced functionality as part of a complete Crestron automation system. Integrating HVAC with a Crestron system can help lower energy bills and increase user friendliness.

    Specifications

    Wireless
    • RF Transceiver infiNET EX circledR; 2-way RF, 2.4 GHz ISM Channels 11-26 (2400 to 2483.5 MHz), default channel 15; IEEE 802.15.4 compliant
    • Range (typical) 150 ft (46 m) indoor, 250 ft (76 m) outdoor to nearest mesh network device(s); subject to site-specific conditions and individual device capabilities[3]
    • Gateway Requires an infiNET EX gateway[4]
    Connectors
    • HVAC CHV-TSTATEX Model:
    • 7 terminal blocks comprising the following (top row, listed left to right):
    • RS2: Remote sensor 2 (outdoor)
    • RS1: Remote sensor 1 (indoor)
    • RSR: Remote sensor return
    • RSR: Remote sensor return (duplicated for easier wiring)
    • W2: Heat, second stage
    • W1: Heat, first stage
    • RH: Heat return
      • 7 terminal blocks comprising the following (bottom row, listed left to right)
      • B: Auto changeover (inverted); switched to RC during heat calls
      • O: Auto changeover; switched to RC during cool calls
      • G: Fan
      • Y2: Cool, second stage
      • Y1: Cool, first stage
      • RC: Cool return
      • C: 24 VAC common
        • CHV-TSTATEX FCU Model:
        • 7 terminal blocks comprising the following (top row, listed left to right):
        • RS2: Remote sensor 2 (outdoor)
        • RS1: Remote sensor 1 (indoor)
        • RSR: Remote sensor return
        • RSR: Remote sensor return (duplicated for easier wiring)
        • N/C: Unused
        • W: Heat
        • N/C: Unused
          • 7 terminal blocks comprising the following (bottom row, listed left to right):
          • 24C: 24V supply
          • R: 24V return
          • Y: Cool
          • N/C: Unused
          • GH: Fan high
          • GM: Fan medium
          • GL: Fan low
          Buttons
          • MODE Cycles through available System Modes: OFF, HEAT, AUX HEAT ONLY (for heatpump or dual-fuel systems only), and COOL
          • FAN Toggles fan setting between FAN AUTO and FAN ON
          • RAISE Raises the set point
          • LOWER Lowers the set point
          • HOLD (combination) Pressing MODE and FAN buttons simultaneously enters/EX ts HOLD mode
          • SETUP (combination) Holding the FAN button, then pressing the RAISE and LOWER buttons simultaneously for 5 seconds enters SETUP mode; pressing mode button advances to nEX setup parameter/function; pressing RAISE or LOWER adjusts value of current setup parameter or EX cutes current setup function; pressing FAN button EX ts SETUP mode
          Display
          • Type Backlit LCD with (2) large 7-segment digits, (2) small 7-segment digits, (14) dedicated symbols;
          • Displays ambient temperature, set point, system mode, fan setting, call activity, low battery, RF or control system communication errors, firmware download progress, setup parameter/function and value
          Measurement Range
          • Ambient Temperature -10° to 110°F (-23° to 43°C)
          • Display Limits -9° to 99°F (-9° to 43°C)
          Temperature Tolerance
          • Over Full Range 1F (0.5C)
          • At Room Temperatures 1F (+0.4/-0.2C)
          Setpoint Range
          • Heat Set Point 38° to 89°F (3° to 32°C)
          • Cool Set Point 59° to 99°F (15° to 37°C), or 38° to 99°F (3° to 37°C) EX ended cool mode enabled
          Relay Rating
          • 1 Amp @ 40 Volts DC or 24 Volts AC (nominal)
          Environmental
          • Temperature -10° to 110°F (-23° to 43°C)
          • Humidity 10% to 90% RH (non-condensing)
          Power Requirements
          • 24V 0.24 Watts (10 mA) @ 24 Volts AC, supplied by heating or cooling system
          • Battery (2) AA batteries required, estimated 1 year normal operation
          Housing
          • Plastic, surface-mountable to the front of a horizontally oriented 1-gang electrical box
          Dimensions
          • Height 4.51 in (115 mm)
          • Width 5.50 in (141 mm)
          • Depth 1.02 in (26 mm)
          Weight
          • 6.7 oz(190 g)

          Additional Information

          Key Features
          • Wall mount heat/cool thermostat for baseboard, forced air, and heat pump[1] HVAC systems
          • Crestron system integration via infiNET EX circledR; wireless network
          • Saves on energy costs with advanced programming abilities
          • Supports two remote temperature sensors
          • Fail-safe mode allows operation in event of control system failure
          • Backlit LCD display
          • Fan coil unit control[2] (CHV-TSTATEX FCU model only)
          • Available in white, black, or almond finish