Load Control |
Switched Load Types | Bidirectional motor |
Motor Control Channels | One channel comprised of two interlocking switched outputs, one for "raise/open" and one for "lower/close" |
Load Rating | 2.5 Amps FLA, 15 Amps LRA, for use with loads having a power factor of 0.50 or greater |
Live/Load Voltage | 230 Volts AC, 50/60Hz |
Connections |
L | (3) Captive screw terminals, paralleled, Live power input and hardwire pass-throughs |
N | (4) Captive screw terminals, paralleled, Neutral connections |
G | (2) Captive screw terminals, paralleled, Ground connections |
R | (1) Captive screw terminal, Remote control switch input (230V SPST normally-open momentary or maintained contact) |
SW1 | (1) Captive screw terminal, raise/open switched load output |
SW2 | (1) Captive screw terminal, lower/close switched load output |
Each terminal accepts a single 1-2.5 mm² (18-14 AWG) conductor. |
Controls & Indicators |
Setup | (1) Pushbutton, for manual operation and wireless network setup |
Chan. 1 | (1) Green LED, indicates raise/open output is switched on, also used for setup |
Chan. 2 | (1) Green LED, indicates lower/close output is switched on, also used for setup |
Wireless Communications |
RF Transceiver | infiNET EX 2-way RF, 2.4 GHz ISM channels 11-26 (2400 to 2483.5 MHz), default channel 15; IEEE 802.15.4 compliant, AES-128 encryption |
Range (typical) | 15 m (50 ft) to gateway or nearest mesh network device(s), subject to site-specific conditions and individual device capabilities, range between floors or ceilings is limited to one level [1] |
Gateway | Requires an infiNET EX gateway (sold separately) |
Construction |
Plastic surface-mount housing, suitable for installation in a non-plenum ceiling space |
Environmental |
Temperature | 0° to 40° C (32° to 104° F) |
Humidity | 10% to 90% RH (non-condensing) |
Dimensions |
Height | 41 mm (1.61 in) |
Width | 55 mm (2.13 in) |
Length | 178 mm (7.00 in) |
Weight |
199 g (7 oz) |
Compliance |
CE, c-Tick, EAC |