Key Features
  • 2M wide DIN rail mounting
  • Controls up to 250 objects on a KNX network
  • Ethernet control
  • No polling necessary - sends live updates
  • Capable of addressing and controlling separate KNX objects
Price: CALL
    Quantity:
    Availability: In Stock
    Usually ships In 24 - 48 hours

    Item #: CI-KNX

    Description

    The CI-KNX provides a bi-directional Ethernet interface to a KNX network.

    It is capable of addressing and controlling up to 250 KNX/EIB objects. The CI-KNX contains a TCP/IP port for communication and Power-over-Ethernet (PoE). Easy programming using ETS (KNX/EIB) programming software makes it ideal for small EIB/KNX installations while maintaining scalability for bigger projects.

    Specifications

    Power Requirements
    Power Supply12–24 VAC, 12–30 VDC power supply or
    Power-over-Ethernet (PoE) 802.3af;
    (Power supply sold separately)
    Power Consumption0.8 W (0.02 A @ 24 VDC)
    Connectors
    Power(2) Screw terminals
    LAN(1) 8-wire RJ-45 connector;
    10/100 Base-T Ethernet port (IEEE802.3af)
    BUS (KNX/EIB)(1) Wago connector;
    Connects to the KNX bus
    Controls and Indicators
    KNX LED(1) Green LED;
    Lights to indicate bus voltage on KNX;
    Flashes to indicate telegram traffic
    Ethernet LED(1) Green LED;
    Lights to indicate Ethernet connection;
    Flashes to indicate Ethernet traffic
    Programming Button(1) Recessed pushbutton;
    Used to enter ETS programming mode
    Programming LED(1) Red LED;
    Lights when the CI-KNX is in ETS programming mode
    Environmental
    Temperature (operating)-5° to 45°C (23° to 113°F)
    Temperature (nonoperating)-25° to 70°C (-13° to 158°F)
    Humidity5% to 93% RH (noncondensing)
    Construction
    Light gray polycarbonate housing, 35 mm DIN EN 60715 rail mount, occupies 2 DIN module spaces (36 mm)
    Dimensions
    Height88 mm (3.47 in)
    Width35 mm (1.38 in)
    Depth58 mm (2.28 in)
    Weight
    100 g (3.5 oz)
    Compliance
    LVD 2006/95/EG, EMC 2004/108/EG, EN 50090-2-2:2007 (HBES), EN 61000-6-2:2005 (susceptibility), EN 6100‑6‑3:2007 (Emissions)